1 / 2
1 / 2
Description
Overview
SPX FLOW APV CU4 Direct Connect Control Unit (Form No. H323871, Revision GB-9) operates as the electro-pneumatic interface between PLC control and sanitary process valves in food, dairy, and beverage lines. It houses 1 or 3 pilot solenoid valves, an electronic module with PWM solenoid control and galvanic separation, two adjustable Hall effect position sensors (or external inductive proximity switch inputs), and external LED indicators visible through the cover window.
Features and Modular Variants
- Modular building-block design: swapping the electronic module converts between Direct Connect, AS-interface, Profibus, and DeviceNet (with corresponding wiring change)
- Integrated exchangeable air particle filter and exhaust silencers on pneumatic connections
- Supply and exhaust throttling screws on the first solenoid valve allow adjustment of actuator operating speed to prevent pressure hammer
- Integrated pressure relief valve in the control unit base prevents internal overpressure
- Variants by valve duty:
- CU41-T-DC: Internal air transfer (
P,Y1,A1) for valves with turning actuators (butterfly valves) - CU41-S-DC / CU41-M-DC / CU41-D4: 1 solenoid valve for single-seat valves and double-seat mixproof valves without seat lift
- CU41N-S-DC: 1 solenoid valve with logic NOT element (external reducing valve fixed at 5 bar max.) to boost actuator closing spring force via port
N - CU43-M-DC / CU43-D4: 3 solenoid valves (
Y1main actuator,Y2upper seat lift,Y3lower seat lift) for double-seat mixproof valves with seat lift
- CU41-T-DC: Internal air transfer (
Technical Data
| Parameter | Specification |
|---|---|
| Housing Material | PA6.6 |
| Protection Class & Standards | IP 67 (EN 60529), EMC 2014/30/EU (EN 61000-6-2, EN 61000-6-4), EN 60068-2-6, DIN EN ISO 13849-1, RoHS 2011/65/EU |
| Ambient Temperature | -20 °C to +70 °C |
| Air Hose & Pressure Range | 6 mm / 1/4” OD; 6–8 bar dry, clean compressed air |
| Compressed Air Quality (DIN ISO 8573-1) | Solid particles class 3 (max. 10000 of 0,5 < d < 1,0 µm; 500 of 1,0 < d < 5,0 µm per m³); water class 3 (max. dew point -20 °C); oil class 1 (max. 0,01 mg/m³) |
| Operating Voltage | 15 – 24 VDC |
| Digital Inputs (DI) | 15 – 48 VDC, Imax 1 mA / 24 VDC, threshold 5 V to 7 V |
| Digital Outputs (DO) | Umax 48 VDC, Imax 150 mA, RI 5,6 Ohm / 100 mA |
| Sensor Supply | 5 VDC (+/-5%), 4,75–5,25 VDC |
| Power Consumption (at 24 VDC) | Min. ~20 mA (no solenoid); typical ~35 mA (1 solenoid); max. ~55 mA (3 LEDs, 2 solenoids) |
| Terminal Cross Section | 0,5–1,5 mm² (AWG 20–16) with conductor sleeve |
Electrical Connections and Sensors
| Terminal | CU41 M12 5-pin | CU43 M12 8-pin | Designation | Function |
|---|---|---|---|---|
| 1 | 1 brown | 2 brown | Power | Operating voltage |
| 2 | 3 blue | 7 blue | Power | Operating voltage |
| 3 | 2 white | 3 green | DO Closed Valve | Potential-free digital output (closed) |
| 4 | 5 grey | 1 white | DO Open Valve | Potential-free digital output (open) |
| 5 | Bridge to 1 | Bridge to 1 | DO Common | Common potential for feedback outputs |
| 6 | 4 black | 6 pink | DI Main Valve | Controls 1st solenoid valve (valve open) |
| 7 | — | 4 yellow | DI Upper Seat Lift | Controls 2nd solenoid valve (upper seat lift) |
| 8 | — | 8 red | DI Lower Seat Lift | Controls 3rd solenoid valve (lower seat lift) |
| 9 | Bridge to 2 | 5 grey | DI Common | Common potential for digital inputs |
- Internal Hall sensors:
H320385(APV valves) andH337014(APV / WCB D4 valves) - External inductive proximity switch:
H208844 - External LED diagnostics: Green solid (Valve Open), Orange solid (Valve Closed), Green Power Diagnose solid/flashing (faultless / solenoid wire fracture), Blue Solenoid Main solid (main valve) or 1 blink / 2 blinks (upper / lower seat lift).
Ordering Information
When requesting a quote for SPX FLOW APV CU4 control units, share the 6-digit APV H-number from the housing label (or target valve series, adapter type, M12 vs. cable gland wiring, and quantity).